E5AR-T.pdf 데이터시트 (총 16 페이지) - 파일 다운로드 E5AR-T 데이타시트 다운로드

No Preview Available !

Advanced Digital Temperature Controller
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
www.DataSheet4U.com
CSM_E5AN-H_E5EN-H_DS_E_3_2
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller. Models also
available with Remote SP.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
• Model available with position-proportional control
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
Refer to Safety Precautions for E5@N/E5@N-H.
Refer to Operation for E5@N/E5@N-H for operating
procedures.
Main I/O Functions
Remote SP Input
One
Event Inputs
None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
Thermocouple/Pt input:
±0.1% of PV
Analog input:
±0.1% FS
Sampling Period
60 ms
PF Key
(Programmable
key function)
E5AN-H
E5EN-H
3-level Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit Display with high resolution of 0.01°C
Infrared port
USB
Auxiliary Outputs
• Two
• Three
Computer Support Software
CX-Thermo
Control Output 2
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
Models available with
RS-485, RS-422, or
RS-232C
communications
Control Output 1
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
1

No Preview Available !

Lineup
E5AN-H/E5EN-H
www.DataSheet4U.com
E5AN-H/E5EN-H
Advanced Type
Terminal block
Fully universal input
1 control output
2 auxiliary outputs
2 control outputs
2 auxiliary outputs
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
Model Number Structure
Model Number Legend
Controllers
E5AN/E5EN-@@@@@@@M@-@-500
1 2 3 4 5 6 7 8 9 10 11
1. Type
H: Advanced
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
3. Control Output 1
A: Control Output Unit
R: Relay output
S: SSR output
4. Control Output 2
A: Control Output Unit
R: Relay output
S: SSR output
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
W: Silver
11.Terminal Cover
-500: With Terminal Cover
Option Units
E53-@
1
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
Output Units
E53-@@
12
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
2. Version
Blank: Available for E5AN-E5EN-H and E5AK/E5EK.
N: Available only for E5AN-H/E5EN-H.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
2

No Preview Available !

Ordering Information
E5AN-H
Size
Case
color
Power
supply
voltage
Control Auxiliary
method output
Control output 1/2
Control Output Unit × 2
2
Basic
100 to
240 VAC
3
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Black
Valve 2
1/4 DIN
96 × 96 × 78
(W × H × D)
2
Basic
24 VAC/
VDC
3
Relay outputs × 2
Relay outputs × 2
Control Output Unit × 2
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Valve 2
Relay outputs × 2
Relay outputs × 2
100 to
240 VAC
Silver
Basic
24 VAC/
VDC
2
Control Output Unit × 2
Control Output Unit × 2
Control Output Unit × 2
E5AN-H/E5EN-H
www.DataSheet4U.com
Optional functions
Heater
burnout Event Transfer
inputs output
RSP
Model
12
4 to 20-mA
input
E5AN-HAA2HBM-500
12
4 to 20-mA
input
E5AN-HSS2HBM-500
2
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HAA2HHBFM-500
2
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HSS2HHBFM-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HAA3BFM-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HSS3BFM-500
2
4 to 20-mA
input
E5AN-HPRR2BM-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HPRR2BFM-500
12
4 to 20-mA
input
E5AN-HAA2HBMD-500
12
4 to 20-mA
input
E5AN-HSS2HBMD-500
2
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HAA2HHBFMD-500
2
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HSS2HHBFMD-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HAA3BFMD-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HSS3BFMD-500
2
4 to 20-mA
input
E5AN-HPRR2BMD-500
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HPRR2BFMD-500
12
4 to 20-mA
input
E5AN-HAA2HBM-W-500
2
2
4 to 20-mA
output
4 to 20-mA
input
E5AN-HAA2HHBFM-W-500
12
4 to 20-mA
input
E5AN-HAA2HBMD-W-500
3

No Preview Available !

E5AN-H/E5EN-H
www.DataSheet4U.com
E5EN-H
Size
Case
color
Power supply
voltage
100 to 240 VAC
Black
1/8 DIN
48 × 96 × 78
(W × H × D)
24 VAC/VDC
100 to 240 VAC
Silver
24 VAC/VDC
Control
method
Auxil-
iary
output
Control output 1/2
Control Output Unit × 2
2
Basic
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Control Output Unit × 2
3
SSR outputs × 2
Valve 2
Relay outputs × 2
Relay outputs × 2
Control Output Unit × 2
2
Basic
SSR outputs × 2
Control Output Unit × 2
SSR outputs × 2
Control Output Unit × 2
3
SSR outputs × 2
Valve 2
Relay outputs × 2
Relay outputs × 2
Control Output Unit × 2
Basic 2
Control Output Unit × 2
Control Output Unit × 2
Heater
Optional Functions
burn- Event Transfer
out inputs output
RSP
12
4 to 20-mA
input
12
4 to 20-mA
input
2
2
4 to 20-mA 4 to 20-mA
output
input
2
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA
input
2
4 to 20-mA 4 to 20-mA
output
input
12
4 to 20-mA
input
12
4 to 20-mA
input
2
2
4 to 20-mA 4 to 20-mA
output
input
2
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA 4 to 20-mA
output
input
2
4 to 20-mA
input
2
4 to 20-mA 4 to 20-mA
output
input
12
4 to 20-mA
input
2
2
4 to 20-mA 4 to 20-mA
output
input
12
4 to 20-mA
input
Model
E5EN-HAA2HBM-500
E5EN-HSS2HBM-500
E5EN-HAA2HHBFM-500
E5EN-HSS2HHBFM-500
E5EN-HAA3BFM-500
E5EN-HSS3BFM-500
E5EN-HPRR2BM-500
E5EN-HPRR2BFM-500
E5EN-HAA2HBMD-500
E5EN-HSS2HBMD-500
E5EN-HAA2HHBFMD-500
E5EN-HSS2HHBFMD-500
E5EN-HAA3BFMD-500
E5EN-HSS3BFMD-500
E5EN-HPRR2BMD-500
E5EN-HPRR2BFMD-500
E5EN-HAA2HBM-W-500
E5EN-HAA2HHBFM-W-500
E5EN-HAA2HBMD-W-500
Accessories (Order Separately)
Output unit Model
Specifications
Relay
output
E53-RN
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
Voltage
output
(for driving
SSR)
E53-QN
E53-Q3
E53-Q4
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
Current
output
E53-C3N
4 to 20-mA DC, load: 600 max.,
resolution: approx. 10,000
E53-C3DN
0 to 20-mA DC, load: 600 max.,
resolution: approx. 10,000
Linear
voltage
output
E53-V34N
E53-V35N
0 to 10 VDC, load: 1 kmin., resolution:
approx. 10,000
0 to 5 VDC, load: 1 kmin., resolution:
approx. 10,000
USB-infrared Conversion Cable
Model
E58-CIFIR
Terminal Cover
Connectable models
Model
E5AN-H
E5EN-H
E53-COV16
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Connectable models
Model
E5AN-H
Y92S-P4
E5EN-H
Y92S-P5
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
Hole diameter
5.8 dia.
12.0 dia.
Model
E54-CT1
E54-CT3
CX-Thermo Support Software
Model
EST2-2C-MV4
USB-Serial Conversion Cable
Model
E58-CIFQ1
4

No Preview Available !

Specifications
E5AN-H/E5EN-H
www.DataSheet4U.com
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Voltage output
(for driving SSR)
Control
output
Current output
Linear voltage output
Built-in SSR output
Relay output for
position-proportional
control
Auxiliary
output
Number of outputs
Output specifications
Event
input
Number of outputs
External contact input
specifications
Number of operations
Logic
Operations
operations
Output
Work bit
assignment
Transfer
outputs
Number of outputs
Output specifications
Number of inputs
Signal type
RSP
input
Analog input scaling
Accuracy
Input sampling period
Setting method
Indication method
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 Mmin. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
Output Unit (Install the Output Unit (sold separately).)
75 to 250 VAC, 1 A (resistive load)
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.
Potentiometer input: Must be between 100 and 2.5 kfor maximum open position.
2 or 3 max.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
2 or 4 (with an E53-AKB)
Contact input: ON: 1 kmax., OFF: 100 kmin.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
8 max.
Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
Output inversion: Possible
One work bit per operation
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary
outputs, or control outputs.
1 max. (Depends on model. Models with transfer output (F in model number)
Current output: 4 to 20 mA DC, Load: 600 max., Resolution at 4 to 20 mA: Approx. 10,000
1
Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Scaling of signal to engineering units (EU)
19,999 to 30,000 (display: 30,000 max.)
(±0.2% of FS) ±1 digit max.
60 ms
Set digitally using keys on the front panel or by using the RSP input.
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40%
AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output
ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling
coefficient adjustment
10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C
25% to 85%
25 to 65°C (with no condensation or icing)
5